Diesel engine instability

Date:2016-09-24 09:27:48

the reason:
A) The fuel pipe is blocked
B) Fuel pump failure
C) The fuel filter is dirty
D) governor spring adjustment / improper assembly
E) Injector malfunction or incorrect injector type
F) Fuel tank ventilation is blocked
G) The fuel system has air
H) The air filter is blocked or the type is not correct
I) Engine speed control system moving parts jamming
J) Engine temperature is too high
K) Valve clearance is incorrect
L) Excessive lubricating oil, or the use of lubricating oil varieties grade wrong
M) The cold start system is faulty
N) The exhaust pipe is blocked
O) Fuel pump failure
P) The compression pressure is low
Q) Valve stuck
R) high-pressure tubing wrong or wrong
S) Valve spring is broken

Approach:
A) Check / replace the fuel line
B) Check / repair oil pump and replace if necessary
C) Replace the fuel filter
D) Adjust / replace governor spring
E) Check / adjust or replace the injector
F) Clean / install ventilation tube
G) Discharge air from the fuel
H) Replace the air filter / Make sure to install the correct air filter for the model
I) inspection, cleaning
J) See "Coolant temperature is higher than normal."
K) Check / adjust the valve clearance
L) Check and adjust the oil or replace the oil varieties, grades
M) Install the cold start auxiliary device. Check, repair cold start device, if necessary, replace
N) Check and remove the blockage. Check the exhaust pipe size is correct
O) Please contact your dealer
P) See "Low Compression Pressure"
Q) Clean the valve stem and the conduit hole
R) corrected or replaced
S) Replace valve spring